ENERGY SAVING SOLUTIONS
 
 
Previous  Application   Next Application
     
Sleep & wake-up mode:
Sleep mode & wake-up mode facility has provided to avoid unnecessary utilization of power when required pressure level has reached in pipe & there is no discharge from pipe. In this condition PLC will observe the present pressure & motor RPM & will forced the drive in sleep mode. When water discharge will take place through pipe pressure start reducing in pipe, this will detect by PLC & when pressure falls below the preset level PLC will restart the drive to maintain the pressure in pipe which is called the wake-up mode of drive.

  Dry run of the pumps:
If water level of the tank falls below the suction level, level transmitter located inside the tank will give the feed back to the PLC & PLC will shut down all the running pumps to avoid the dry run of the pumps. By using level signal one relay will be activated & through one of the relay contact i/p will be given to PLC & through another relay contact manual operations of the pumps will be also
stopped.

Alarms alerts:
If any fault generates in VFD, by using VFD relay contact input will be given to PLC & after detecting alarm from drive, PLC will stop the system to avoid accident. Also from over load relay auxiliary contact of each star-delta starter one input will given to PLC to acknowledge the trip indication of star-delta starter & to take the necessary action. To give the alarm annunciation signal to operator one Hooter & indicator will be connected on the panel. Input signal to the hooter & indicator will be given by combining all the alarm signals from star-delta starter & VFD. One relay will be activated if any one alarm will be occurred & by using contact of this relay Hooter will be activated. If operator want to reset the generated alarm one switch will be provided on the panel.
 
 
System status display:
To give the online status information of the system to the operator, status indicator will be provided on the panel. With this operator will come to know that which pump is running on VFD, which auxiliary pump is running & so on.

Operator interface unit:
OIU is connected to the PLC. In addition to the system status indication OIU will be used to show the system status in alphanumerical format. Also with the help of OIU the necessary parameter from PLC such like sleep mode, wake-up mode set points, drive set point, second star-delta & third star-delta start & stop set point, friction loss compensation set point can be edited as per user demands.

Manual operations:
If VFD will fail or as per operator requirement operator will put the system in manual mode. For change over from Auto to manual & Manual to Auto one selector switch will be provided on panel. In manual mode first pump of the series will come on VFD & remaining two pumps can be started on star-delta as per requirement. In manual mode all the operations will be performed manually by using buttons provided on panel & PLC will get bypass.
 
 
   
 
 